HGM170HC Genset Controller

DESCRIPTION
The Model 170/170hc is an Automatic Engine Control Module. The module is used to automatically start and stop the engine, indicating the operational status and fault conditions, automatically shutting down the engine and indicating the engine failure by LED on the front panel. HGM170hc append a LCD hours count that base on HGM170.

OPERATION

Operation of the module is via a three position key switch mounted on the front panel with OFF(O), STARTand AUTO positions. In the ‘O’ position the output are de-energized.
Manual Operation:
1. Select manual run
2. Depress pre-heat button for required length of time
3. Press START
to crank engineOnce the Start button is pressed and maintained, the engine fuel system is energized. The ‘Crank’ output is then energized and the starter motor operated, disengaging automatically when the engine fires or when the ‘Start’ button is released. The protection hold-off timer is then initiated.
Automatic Operation:
1. Select AUTO
2. When Remote Startis active, the generator will automatic start.Operation of any of the following alarms (which are close on fault) will cause the run output to de-energize. Low Oil Pressure. High Engine Temperature.Auxiliary ShutdownOver speedThis will remove the fuel supply from the engine and bring it to rest. Each alarm has its own LED indicator and once activated no further alarm conditions will be accepted. The alarm output and relevant LED will remain active until the unit is reset by turning the switch to the ‘O’ position.

Over speed Protection

Over speed protection is derived from the generator Hz output. The over frequency circuit monitors the generator Hz output and will shut down the engine immediately if a pre-set frequency level is exceeded. This trip level is selected by a switch for either 50Hz or 60Hz nominal operation (57Hz or 68Hz trip respectively).During engine cranking and for a short time afterwards the protection hold-off timer(10 seconds) is active and the relevant alarm inputs are inhibited. This enables the engine to start and achieve normal running conditions. Once the timer has expired the inputs are enabled providing normal protection from the module.

Charge Failure warning

Charge Failure warning is also provided by monitoring the WL terminal on the charge alternator. This operates on a similar principal to the warning lamp fitted in a motor vehicle, should the output fail the charge fail LED will illuminate. The module will also provide the alternator excitation current via this connection.

Specification

DC Supply:8 to 35 V Continuous.
Alternator Input Range:15 - 306VAC(+20%) RMS
Alternator Input Frequency:50 - 60 Hz at rated engine speed.Over speed: nominal frequency +14% (+24% Overshoot)
Start Output:Solid State 1.2A negative grounding terminal
Fuel Output:Solid State 1.2A negative grounding terminal
Pre-heat Output:Solid State1.2A negative grounding terminal
Operating Temperature Range:-30 to +70°C


Service Support
Download
Products News
Contact Us
TEL:0086-371-67981000
FAX:0086-371-67992952
E-mail:sales@smartgen.cn
MSN: TERRY SARA  
SKYPE: ICY ICY SUMMER SUMMER
FOLLOWING US @:Facebook@Smartgen Technology   Twitter@Smartgen Technology   Google+@Smartgen Technology   
WEB:中文  繁體  English  العربية  Français  Español  Português  русский  South Africa agent   
ADD:No.28 Jinsou Road, Zhengzhou City, Henan Province, China  
TEL:0086-371-67981000(overseas)/67988888  
FAX:0086-371-67992952  
E-MAIL:sales@smartgen.cn    


        
Copyright © 2012 Smartgen